Vue de la page 30
RT9 Powershelf Rectifier Technologies
158-1806-01.doc
31 2-Mar-06
(Base Menu continued)
ENTER
3-ph AC Monitor
Off
INC/DEC toggles state
ENTER to accept
(If 3-ph AC Monitor not = Off) ENTER
3ph AC Vhi Alarm
260V
Modify Value up/down
ENTER to accept
ENTER
3ph AC Vlo Alarm
200V
Modify Value up/down
ENTER to accept
ENTER
3ph AC fhi Alarm
55.0Hz
Modify Value up/down
ENTER to accept
ENTER
3ph AC flo Alarm
45.0Hz
Modify Value up/down
ENTER to accept
ENTER
3ph AC FS Curr.
100A
Modify Value up/down
ENTER to accept
ENTER
Battery Monitor
Off
INC/DEC toggles state
ENTER to accept
(If Battery Monitor not = Off) ENTER Selects battery cell type
Battery Config
24 cells
Modify Value up/down
ENTER to accept
ENTER Number of battery banks
BCM Batteries
1
Modify Value up/down
ENTER to accept
ENTER
Cell Vhi Alarm
2.50V
Modify Value up/down
ENTER to accept
ENTER
Cell Vlo Alarm
1.80V
Modify Value up/down
ENTER to accept
ENTER Differential cell threshold
Cell +dVc Alarm
10%
Modify Value up/down
ENTER to accept
ENTER Differential cell threshold
Cell -dVc Alarm
10%
Modify Value up/down
ENTER to accept
ENTER
Site Monitor
Off
INC/DEC toggles state
ENTER to accept
(If Site Monitor not = Off) ENTER Status of output relay 1
Output 1
Off
Modify Value up/down
ENTER to accept
ENTER Status of output relay 2
Output 2
Off
Modify Value up/down
ENTER to accept
ENTER Status of output relay 3
Output 3
Off
Modify Value up/down
ENTER to accept
ENTER Status of output relay 4
Output 4
Off
Modify Value up/down
ENTER to accept