RT9-48V/1.4kW Rectifier Specification
Rectifier Technologies Pacific Page 1 of 6
18 Joseph Street, Blackburn North,
Victoria 3130 Australia 25/03/2010
http://www.rtp.com.au 950-1712-05 RT9 48V-1.4kW.doc
The RT9-48V/1.4kW is a switched mode rectifier
(SMR) module that delivers up to 1.4kW of output
power (and up to 30A output current) into a 48V
nominal DC system. The RT9 suits AC supply
voltages between 208 and 240VAC but will also
operate at reduced power from supplies as low as
100VAC. The RT9 may be safely hot-plugged into
a live system for convenient system expansion or
module replacement.
Rectifiers convert power from an AC supply into
smooth DC, and are normally used in conjunction
with a battery to provide an uninterruptible DC
power system. A number of SMR modules (N) are
commonly used in parallel to deliver the required
power, with one or more additional modules (N+1)
providing redundancy.
The small dimensions of the RT9 allow high power
density in 300, 400, or 600mm deep 19-inch or 23-
inch racks. The addition of a supervisory and
control unit (CSU) allows a sophisticated power
system to be built with network connectivity and
remote asset management features.
Operating characteristics of the RT9-48V/1.4kW at 25°C, 230VAC, 50Hz unless otherwise stated:
Input AC
Voltage:
Single phase: Active, Neutral, and Earth.
Rated voltage range: 100 – 240VAC;
Rated voltage tolerance: 85 – 275VAC;
Maximum voltage before shutdown 300VAC;
Full output power available above 185VAC;
Reduced output power from 85 – 185VAC;
(Available power varies from 560W – 1400W);
At 100VAC, 680W available;
At 120VAC, 850W available;
Current:
9.5A RMS max line current at 185VAC;
7.5A RMS line current at 230 VAC;
Current limited to 10A or less below 185VAC;
Frequency:
45 - 66Hz;
Inrush Current:
< 9A RMS;
Soft Start:
Output current ramp-up time 8 seconds to 25A;
Harmonic Distortion:
Current THD < 5% typically at full output power
when operated with mains voltage THD < 2%;
Power Factor:
> 0.98 for >50% output power;
> 0.99 for 100% output power;
Reduced power factor above 275VAC
Protection:
Fully protected up to 440VAC;
Varistors provide surge protection;
Two internal fuses provided;
SMR is turned off if the AC voltage exceeds
~305VAC or falls to less than ~70VAC; SMR re-
activates when AC voltage is within approximately
83 – 285 VAC;
Input inrush limiting circuit prevents high surge
currents during a hot-plug installation;
Voltage Withstand Test:
1500VAC input to chassis for 1 minute;
(2200VDC 100% testing on production units for 2
seconds);
Efficiency:
> 90% typical from 50% to 100% output power;